Açıklama
Code |
CF30001G |
CF30002G |
CF30004G |
---|---|---|---|
Description | 1 Loop Control Panel | 2 Loop Control Panel | 4 Loop Control Panel |
Standards |
EN54 Pt2, 1997, A1:2006, EN54 Pt4, 1997, A1:2002, A2:2006 EN54 Pt13: 2005 |
||
Specification | |||
Number of Loops |
1 |
2 |
4 |
Addresses per Loop |
200 |
||
Number of conventional sounder circuits |
4 monitored for open and short circuit |
||
Auxiliary Fire Routing Equipment Output (Monitored) |
24V 30 mA (max) |
||
Auxiliary Fault Protection Equipment Output (Monitored) |
24V 30 mA (max) |
||
Auxiliary Fault Routing Equipment Output (Monitored) |
12V 30 mA |
||
System Operating Voltage |
24V dc (nom) |
||
Mains Input Supply |
230V ac +1%/-15% |
||
Class Change Facility |
Terminals for connection of external contacts, can also be instigated via input interface |
||
Auxiliary Relay |
1 set of changeover contacts operate in event of fire condition |
||
Output Ports |
RS485, RS232 for connection of repeaters etc |
||
Standby Duration |
Dependent on loop loading and battery configuration |
||
Battery | 2 x 12Ah (standard versions) | 2 x 12Ah (standard versions) 4 x 12Ah (EB versions) | 2 x 12Ah (standard versions) 4 x 12Ah (EB versions) |
Environmental | |||
Operating Temperature |
-5OC – +40OC |
||
Humidity (Non Condensing) |
0 to 75% RH |
||
Physical | |||
Construction |
Back – Box – Mild Steel, Front Door – PC/ABS |
||
Dimensions (HxWxD) | Standard Versions: 397mm x 497mm x 180mm |
Standard Versions: 397mm x 497mm x 180mm EB Versions: 397mm x 497mm x 280mm |
|
Weight |
18kg |
||
Ingress Protection |
IP30 |
||
Cable entries |
Top: 31 cable knockouts (20mm) Back: 12 cable knockouts (20mm) |
||
System Networking |
Fully networkable up to 126 panels (requires additional network card – 1 per panel) |
İncelemeler
Henüz yorum yapılmadı.